OPzS – Blocks

TAB OPzS stationary battery blocks (cells) are manufactured using conventional lead-acid battery technology.

OPzS stationary batteries are designed to power telecommunications equipment, computers, emergency lighting, alarm systems, control and monitoring in power plants and distribution stations, railway stations, airports, etc.

UF_V/Cela 1,80 1,77 1,75 1,67 EN/IEC 60896-11 Dimensions Weight
Discharge time (h)
10
5
3
1
Ri
Isc
L
W
H
with electrolyte
dry
Type
Ah
Ah
Ah
Ah
kA
mm
mm
mm
kg
kg
12V 1 OPzS 50
51.0
40.9
38.0
28.4
20.00
613
272
205
392
39
26
12V 2 OPzS 100
103.0
81.8
75.7
56.7
9.30
1290
272
205
392
50
38
12V 3 OPzS 150
154.0
122.6
113.7
85.1
6.90
1739
380
205
392
69
53
6V 4 OPzS 200
204.0
167.0
149.3
115.2
2.20
2703
272
205
392
47
36
6V 5 OPzS 250
255.0
208.6
186.6
143.6
1.90
3175
380
205
392
61
44
6V 6 OPzS 300
307.0
250.5
223.7
172.0
1.60
3846
380
205
392
68
52

Electrolyte density: 1.24 ± 0.01 kg/l at 20°C. All measurements and weights are within standard production tolerances. Weight tolerance is ± 5%. Electrical values are approximate. Technical modifications are reserved without prior notice.